T-3202
ONE (1) 5000/6250/7000 KVA ALLIS CHALMERS LOAD TAP CHANGING SUBSTATION
TRANSFORMER, 3 PHASE, 60 HERTZ, 55/65 DEGREE C RISE, CLASS OA/FA,
6.8% IMPEDANCE, ALUMINUM WINDINGS, SERIES WINDING COPPER, HV COVER,
LV THROAT, S/N 5899185
HIGH VOLTAGE: 26400 DELTA BIL: 200 KV
LOW VOLTAGE: 4160Y/2400 BIL: 75 KV
TAPS: 27650-27100-26400-25700-25000
LTC TAPS: 4576 - 3744 +/- 10% IN 32 STEPS
TOTAL WEIGHT: 44,500 LBS.
CORE & COILS: 15,800 LBS.
TANK & FIT.: 11,147 LBS.
OIL: 17,553 LBS. (2,336 GALS.)
DIMENSIONS: 140.5"H X 138"L X 112"W (123.75"H W/O HV BUSHINGS)
RETURN
to our home page