ONE (1) 15/16.8/20/22.4/25/28 MVA COOPER POWER SYSTEMS SUBSTATION TRANSFORMER,
3 PHASE, 60 HERTZ, CLASS OA/FA/FA, 55/65 DEG. C RISE, 9.0% IMPEDANCE,
COPPER WINDINGS, DETACHABLE RADIATORS, 6 X 600:5 HV MRCT'S C200, 6 X
4000:5 LV MRCT'S C800, 1 X 600:5 NEUTRAL MRCT C200, MFG. 1993
HIGH VOLTAGE: 69000 DELTA BIL: 350 KV
LOW VOLTAGE: 4160Y/2400 BIL: 75 KV
TAPS: 72450-70725-69000-67275-65550
TOTAL WEIGHT: 71,690 LBS.
CORE & COILS: 30,300 LBS.
TANK & FIT.: 13,260 LBS.
MAIN TANK OIL: 15,150 LBS. (2,020 GALS.)
RADIATOR OIL: 3,640 LBS. (485 GALS.)
DIMENSIONS: 180.5"H X 181"L X 157"W
SHIPPING: 167.5"H X 120"L X 88"W