41.25/55/68.75 MVA 230KV Y - 6900Y, 4160Y Split Secondary Hyundai LTC Substation
- Manufacturer
- Hyundai
- Model
- LTC Substation
- Condition
- Used
Description
41.25/55/68.75 MVA 230KV Y - 6900Y, 4160Y Split Secondary Hyundai LTC Substation One (1) 41.25/55/68.75 MVA Split Secondary Hyundai LTC Substation Transformer 3 Ph, 60 Hz, ONAN/ONAF1/ONAF2, 65 Deg C Rise, Zero Sequence Imp. 7.77%, Oil Preservation System (Rubber Bag), All Copper Windings, Winding Temp Gauge, Liquid Temp Gauge, Liquid Level Gauge, Vacuum Pressure Gauge, Pressure Release Device, Drain & Sample Valve HV: 230000 Wye BIL: 750 KV (14.75% Imp at 85 DegC) LV(1)(42.5MVA): 6900 Wye BIL: 95 KV (22.58% Imp at 85 DegC) LV(2)(26.25MVA): 4160 Wye BIL: 75 KV (43.56% Imp at 85 DegC) Taps (HV): +/- 10% in 32 steps Total Weight: 250650 lbs Core & Coils: 103600 lbs Tanks & Fitt: 78400 lbs Liquid-Oil: 68650 lbs Shipping Weight: 170000 lbs Shipping Dimensions: 136"H x 106"W x 240"L
Specifications
| Cooling Type | onan_onaf1_onaf2 |
|---|---|
| Core And Coils Weight (kg) | 46,989.4 |
| Frequency (Hz) | 60 |
| Liquid Oil Weight (kg) | 31,137.9 |
| Oil Preservation System | rubber_bag |
| Phase Count | 3 |
| Power Rating Mva | 68.75 |
| Primary Bil (kV) | 750 |
| Primary Impedance Percent At 85c | 14.75 |
| Primary Voltage (v) | 230,000 |
| Primary Winding Configuration | wye |
| Secondary 1 Bil (kV) | 95 |
| Secondary 1 Impedance Percent At 85c | 22.58 |
| Secondary 1 Power Rating Mva | 42.5 |
| Secondary 1 Voltage (v) | 6,900 |
| Secondary 1 Winding Configuration | wye |
| Secondary 2 Bil (kV) | 75 |
| Secondary 2 Impedance Percent At 85c | 43.56 |
| Secondary 2 Power Rating Mva | 26.25 |
| Secondary 2 Voltage (v) | 4,160 |
| Secondary 2 Winding Configuration | wye |
| Shipping Height (m) | 3.454 |
| Shipping Length (m) | 6.096 |
| Shipping Weight (kg) | 77,110.7 |
| Shipping Width (m) | 2.692 |
| Tanks And Fittings Weight (kg) | 35,561.2 |
| Tap Range Percent | 10 |
| Tap Steps | 32 |
| Temperature Rise Deg (c) | 65 |
| Total Weight (kg) | 113,676.5 |
| Winding Material | copper |
| Zero Sequence Impedance Percent | 7.77 |
Request a quote from Belyea Company, Inc.
Tell Belyea Company, Inc. what you need. They'll reply directly to you.
More in Electrical
10 MVA 26400 D - 4160 Y Carte Substation Transformer with LTC
Carte
Belyea Company, Inc.
2500 KVA 13200 Delta 480Y/277 GE Pad-Mount Transformer, DF/RF
GE
Belyea Company, Inc.
1500 KVA 34500 Delta 480Y/277, ABB Substation, Bio-Temp
ABB
Belyea Company, Inc.
3325 KVA Pennsylvania Transformer, 4160 Delta, 2400 Delta, Oil Filled
Pennsylvania
Belyea Company, Inc.
60 MVA 230000GRDY - 115000GRDY x 69000GRDY ABB LTC Auto Transformer
ABB · Dual Secondary LTC Autotransformer
Belyea Company, Inc.
2500 KVA 13200 Delta, 480Y/277 Balteau Pad-Mount Transformer, DF/RF
Balteau
Belyea Company, Inc.