Used Equipment Network
v0 · pilot
20/26.66/33.33 MVA, 115000D - 6900GRDY Virginia Substation Transformer, UNUSED
Electrical·Transformer

20/26.66/33.33 MVA, 115000D - 6900GRDY Virginia Substation Transformer, UNUSED

Sold by Belyea Company, Inc.·Available·Last verified 4h ago
Manufacturer
Virginia Transformer
Condition
Used

Description

20/26.66/33.33 MVA, 115000D - 6900GRDY Virginia Substation Transformer, UNUSED KVA: 20000/26660/33330 KVA Manufacturer: Virginia Transformer Type: Automatic Load Tap Changing Phase: Three HERTZ: 60 CLASS: ONAN/ONAF/ONAF TEMPERATURE RISE: 65 °C IMPEDANCE: 9.43 Primary - First: 115000 V Primary - First Vector: Delta Primary - First BIL: 550 kV Secondary - First: 6900 V Secondary - First Vector: Wye Secondary - First BIL: 110 kV HV BUSHING LOCATION: Top LV BUSHING LOCATION: Top STANDARD TAPS: 120750-117875-115000-112125-109250 On load tap changer: Yes LOW VOLTAGE TAPS: +/- 16 X 0.625% CORE & COIL WEIGHT: 50540 lb TANK & FITTINGS WEIGHT: 40900 lb FLUID WEIGHT: 39750 lb FLUID GALLONS: 5297 gal (US) TOTAL WEIGHT: 138000 lb FLUID TYPE: Mineral Oil LIQUID LEVEL GAUGE: Yes DRAIN & TEST VALVE: Yes TEMPERATURE WINDING GAUGE: Yes

Specifications

Cooling ClassONAN/ONAF/ONAF
Core Coil Weight (kg)22,907.185
Fluid TypeMineral Oil
Fluid Volume Liters20,050.471
Fluid Weight (kg)18,026.455
Frequency (Hz)60
Hv Bushing LocationTop
Impedance Percent9.43
Low Voltage Taps+/- 16 X 0.625%
Lv Bushing LocationTop
Phasethree
Power Rating (kVA)33,330
Primary Bil (kV)550
Primary Vector GroupDelta
Primary Voltage (v)115,000
Secondary Bil (kV)110
Secondary Vector GroupWye
Secondary Voltage (v)6,900
Tank Fittings Weight (kg)18,552.455
Temperature Rise (c)65
Total Weight (kg)62,596.095

Request a quote from Belyea Company, Inc.

Tell Belyea Company, Inc. what you need. They'll reply directly to you.

Your details go directly to Belyea Company, Inc.. We don't share them.