Used Equipment Network
v0 · pilot
7500/9375/10500 KVA, Pri 66000 D, Sec 13800Y/7960, GE LTC SUB, AL-AL, 55/65:
Electrical·Transformer

7500/9375/10500 KVA, Pri 66000 D, Sec 13800Y/7960, GE LTC SUB, AL-AL, 55/65:

Sold by Belyea Company, Inc.·Available·Last verified 5h ago
Manufacturer
General Electric
Model
LTC
Condition
Used

Description

7500/9375/10500 KVA, Pri 66000 D, Sec 13800Y/7960, GE LTC SUB, AL-AL, 55/65: ONE (1) 7500/9375/10500 KVA GENERAL ELECTRIC LTC TRANSFORMER 3 PHASE, 60 HERTZ, CLASS OA/FA, 55/65 DEG. C RISE 8.5% IMPEDANCE, S/N H881716 ALUMINUM WINDINGS (TAP WINDING - COPPER) HSC LOAD TAP CHANGER, 3 X HV CT'S HIGH VOLTAGE: 66000 DELTA BIL: 350 KV LOW VOLTAGE: 13800Y/7960 BIL: 110 KV HV TAPS: 69300-67650-66000-64350-63700 LV TAPS: 12420 - 15180 IN 32 STEPS TOTAL WEIGHT: 45,400 LBS. CORE & COILS: 17,000 LBS. TANK & FIT.: 13,700 LBS. MAIN OIL: 13,600 LBS. (1,820 GALS.) LTC OIL: 1,100 LBS. (150 GALS.) DIMENSIONS: 141.5"H X 117.5"W X 142"D SHIPPING DIMENSIONS: 135"H X 117.5"W X 142"D

Specifications

ClassOA/FA
Core Coils Weight (kg)7,711.065
Depth (m)3.607
Frequency (Hz)60
Height (m)3.592
Hv Bil (kV)350
Hv Taps Count5
Hv Voltage Delta (v)66,000
Impedance Percent8.5
Load Tap Changer TypeHSC
Ltc Oil Gallons150
Ltc Oil Weight (kg)498.95
Lv Bil (kV)110
Lv Taps Count32
Lv Voltage Phase (v)7,960
Lv Voltage Wye (v)13,800
Main Oil Gallons1,820
Main Oil Weight (kg)6,169.265
Phase3
Power Rating (kVA)10,500
Serial NumberH881716
Shipping Height (m)3.429
Tank Fittings Weight (kg)6,213.585
Tap Winding Materialcopper
Temperature Rise (c)65
Total Weight (kg)20,594.265
Width (m)2.984
Winding Materialaluminum